Columbia Boiler MPH 10 HP Bare Boiler Steam boilers

supplied by:

Price: Click To Get Quote

Product Type:
Steam boiler
Competitively-priced, narrow in width & easily serviced, this boiler is a modified Scotch, three-pass fire tube design for use as a 15 PSI steam or 30 PSI water unit. The sizes range from 5 BHP to150 BHP, natural gas or LP gas, #2 oil, dual fuel or biogas fired. Ideal for: breweries, distilleries, schools, apartments, bakeries, brewpubs, laundromats, dairies and many more applications.
MPH Features• 32-1/2” Compact width permits installation through  narrow doors and passageways MPH 5-80• Inverted skid base for forklift handling with low profile• Lifting holes for rigging into tough spots• Bottom hand holes for thorough cleanout• Top hand hole for tube inspection• Cleanout door on flue box• Trim for 15 psi steam or 30 psi water• Modulating burner standard MPH 150, on/off burner MPH 5-20• Natural gas, propane, methane, biogas, oil, or dual fuel firing• Optional hot water coils 300 to 2460 G.P.H.• Overflow tapping for steam unit
• Individual tappings for steam controls• 83%+ efficiency. Economizer package available for high efficiency• Wet base design• Three pass, firetube construction• Welded tubes are schedule 40 pipe for long life 13 Gauge rolled tubes are easily replaced• Fully packaged or knocked down• Forced draft firing, no special vent requirements• Constructed in accordance with requirements of Section IV of the  Boiler and Pressure Vessel Code• All boilers are designed, inspected and stamped for conformity to  the requirements of the National Board of Boiler and Pressure Vessel Inspectors and packaged to meet CSD-1 safety requirements.
MPH SPECIFICATIONS AND DATA - 15 PSI STEAM / 30 PSI WATERMODEL NO. MPH-10Horsepower 9.5Gas Input (BTU/hour) 399,000Oil Input (Gals./hour) 2.85Gross Output (BTU/hour) 331,170Gross Output Steam (Lbs/hour) 320Heating Surface - Sq. Ft. - Pipe 45.6Heating Surface - Sq. Ft. - Tube N/AFurnace Volume - Cu. Ft. 1.9Water Capacity Steam - Gal. 53Steam Volume - Cu. Ft. 3Water Capacity Flooded - Gal. 75Qty. & Length of 2” - 13 ga. Tubes (30) 30-1/8”Hand Hole Quantity & Size N/AStandard Burner Electrical 115/1
WATER COIL DATACoil Model Number (1-1/4” Outlet) #2/3GPM Single Coil - 100° Rise 5GPM Twin Coil - 100° Rise N/A
BOILER DIMENSIONS (INCHES)A Bare Boiler (coil plate to drain) 33.3Burner Plate to Rear T/A 45.75A1 (Turnaround to Turnaround) 46.4B Length (Turnaround to Burner) 58.5C Boiler Width 21.6D Height Supply Outlet 56.5E Minimum Safe Water Level 42.1F Burner Opening to Floor 12.9G Flue Box Height 39.6H Flue Outlet Diameter 8I Safety Valve Opening 1 NPTJ Coil Connections to Floor 46.2K Supply Outlet Location 14.8L Supply Outlet Size 3 NPTM Return Inlet Height 15.3N Return Inlet Size 1.5 NPTO Drain Size 1.25 NPTBoiler Dry Weight - Lbs. 1035
-- [827055] STEAM TRIM MPH10/15
-- [891010] CRT-7 BOILER FEED SYSTEM - Horizontal Low Pressure -- 15PSI steam
-- [827393] GAS BURNER JR15A-12 O/O 
-- [965331] PACKAGE W/J W/TEST
MPH Standard Equipment 
Probe Type Low Water Cut Off and Pump Control, Auxiliary Probe Type LWCO, Operating and Safety Limits, 15 psi ASME Safety Valve and Steam Pressure Gauge.